Home Engineering Tools Cable Sizing & Voltage Drop

Cable Sizing & Voltage Drop Calculator

Calculate low voltage power cable conductor sizes (mm²), continuous current ampacity, voltage drop %, and circuit breaker coordination according to IEC 60364-5-52. Derated for 50 °C Iraqi summer ambient.

IEC 60364-5-52 & IEC 60502-1 Copper & Aluminum (1.5 – 300 mm²) 50 °C Summer Ambient Derated
1
Load & System
2
Installation
3
Length & Cable
4
Results
1. Electrical Load & System Parameters

Enter load rating, voltage system, power factor, and breaker protection type.

System Type & Voltage:
2. Installation Method & Ambient Environment

Select cable routing method, ambient temperature, and cable grouping.

3. Cable Routing Length & Construction

Specify length of run, conductor metal, insulation, and parallel runs.

4. Recommended Conductor Size & Verification

Minimum cross-section to IEC 60364-5-52, voltage drop %, and breaker selection.

Recommended Minimum Conductor Size
35 mm² Cu/XLPE
Derated Ampacity Iz: 118 A | Voltage Drop: 3.07% (12.3V)
Design Current (Ib)
76.4 A
Recommended Breaker (In):
80 A (3P MCCB)
Tabulated Base Ampacity (Itab):
144 A
Derated Cable Ampacity (Iz)
118.1 A
Request Cable Quotation on WhatsApp
Standards & method
IEC 60364-5-52 Low-voltage electrical installations — Selection and erection of electrical equipment — Wiring systems. Defines tabulated ampacities and correction factors.
IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1 kV up to 30 kV.

IEC 60364-5-52 Power Cable Sizing Rules

Selecting low voltage power cables in Iraq requires balancing thermal current capacity (ampacity) against voltage drop over long distribution distances. At peak summer ambient temperatures of 50 °C, standard cable current ratings must be derated significantly to prevent insulation thermal breakdown.

Key Cable Sizing Criteria

Thermal Current Capacity ($I_b \le I_n \le I_z$): The design current $I_b$ must not exceed the protective breaker rating $I_n$, which in turn must not exceed the derated cable ampacity $I_z$.